What it is: A 3-phase UPS designed to make business continuity simple for medium/large commercial buildings and light industrial sites (manufacturing, telecom, healthcare, transportation).
Power range: 250 / 300 / 400 / 500 / 600 kVA (kW) at 400 V class.
Architecture: Fault-tolerant design (power blocks support the load even if one block becomes inoperable, as long as remaining capacity is sufficient).
Efficiency: Up to 96% in double-conversion; up to 99% in ECO mode for lower operating cost.
Parallel & redundancy: Up to 5 UPS in parallel for capacity (or 5+1 for redundancy); supports redundant system architectures (including dual-bus designs).
Electrical performance (typical):
Input: 380/400/415 V (3-phase + N + PE), 40–70 Hz, input PF >0.99, THDi <3%, input voltage range 323–477 V
Output: 380/400/415 V, output voltage tolerance ±1%, load PF compatibility 0.5 leading to 0.5 lagging
Overload (normal operation): 105% continuous, 125% for 10 min, 150% for 1 min
Rugged features (standard): Embedded dust filter, IP20, conformal coating, rodent protection; optional IP31 kit for enhanced protection.
Easy commissioning: Smart Test mode validates UPS performance without a load bank before connecting the load.
HMI & monitoring: 7-inch touchscreen; communication via RS485, dry contacts, Ethernet (SNMP, Modbus TCP/IP, BACnet). Network Management Card included for remote monitoring and EcoStruxure IT integration.
Battery: VRLA, typically 36–50 batteries (depending on configuration); selectable charging power (percentage of output power).
Environment (typical): 0–95% RH non-condensing; up to 1500 m without derating; noise around 70–72 dB (by rating).