What it is: A highly efficient, modular 3-phase UPS for edge, small and medium data centers and critical infrastructure in commercial/industrial facilities.
Power range & scalability: 10–150 kW per UPS; up to 4 UPSs in parallel for up to 600 kW total capacity (capacity or redundancy).
Topology: Online double conversion with modular architecture for fast service and fault tolerance.
Efficiency: Up to 97% in double conversion; up to 99% in ECO and ECOnversion/eConversion high-efficiency modes (model dependent).
Availability features:
N+1 internal module redundancy (one extra power module keeps the load protected with no extra footprint)
Live Swap option (model dependent) to add/replace/remove power modules quickly with minimal downtime risk
Internal maintenance bypass plus optional maintenance bypass panels
Electrical performance:
Unity power factor (PF=1) to right-size to real kW load
Wide input tolerance: ±15% input voltage window; 40–70 Hz input frequency range
Output quality: ±1% voltage regulation; <1% THDU on linear load
Overload (utility operation): 150% for 1 min, 125% for 10 min
Max short-circuit rating: 65 kA; backfeed protection included
Battery flexibility: Supports VRLA and Lithium-ion; available with external batteries or internal smart battery modules (integrated, self-configuring battery strings for predictable runtime and faster expansion).
Monitoring & integration: 4.3" color touchscreen with status LED/mimic; Network Management Card included (Ethernet/SNMP) plus Modbus and 8 dry contacts (4 in / 4 out); EcoStruxure-connected monitoring options.
Rugged deployment: Air filter included and conformal-coated boards; operates at 40°C without derating (50°C with derating); high-elevation capability (no derating up to 3000 m, with derating up to 5000 m); optional ingress-protection kits on select models.